KXM2LE series residual current protected circuit breaker, its rated isolating voltage is 800V, apply to circuit with AC50Hz, rated working voltage 400V, rated current till 800A for infrequent conversion and electric motor infrequent start. Circuit breaker have overload, short circuit and under voltage protection function, can protect circuit and power supply apparatus from being damaged, meanwhile, can provide indirect contact protection to human, also can provide over current protection to non-detectable but long existed ground fault which may have fire risk. Rated residual operation current 30mA circuit breaker have additional protection function to direct contact person while other protection apparatus have fault.
◎Circuit breaker have small volume, high breaking capacity, short arc, anti-shake etc features.
◎Circuit breaker can be installed vertically or horizontally
◎This product according to below criteria:
IEC60947-1 and GB14048.1-2006
IEC60947-2 and GB14048.1-2008
◎Circuit breaker suitable for isolating , express code is " "
Normal working and installation criteria:
◎Surrounding media temperature can't higher than +40℃ or lower than -5℃; and average temperature in 24 hours can't exceed 35℃(except special ordering)
◎Installation place relative humidity can't exceed 50% while max temperature is +40℃,higher relative humidity is acceptable in lower temperature, for example relative humidity can reach 90% at 20℃,should adopt special measure when have condensation dewdrop which caused by temperature changing.
◎Humid tropical type circuit breaker relative humidity can't exceed 95% at +25℃;
◎Pollution degree: III
◎Main circuit of circuit breaker installation type is III, auxiliary circuit and control circuit (non connect to main circuit) installation type is II
◎Circuit breaker apply to electric magnetic surrounding A
◎Humid tropical circuit breaker can resist humid tropical, smoke, mycete affect.
◎Circuit breaker should install in the place without explosion risk, without conducting dust, unable metal corrosive and non-damage isolator
◎Installation place can't hit by rain, snow directly
◎Circuit breaker should install according to instruction.
Accessory
◎Inner accessory:
According to user's demand circuit breaker can lead wire directly(wire length is 1250px, special request should be informed when ordering), or install additional wire terminal.
Shunt trip mechanism (MX) | Rated control power supply voltage (Us)(V) | AC230V,AC400V; DC24V,DC110V,DC220V |
Operation voltage(V) | (0.7-1.1)Us | |
Wire connecting drawing | Note: K-shunt trip mechanism inner microswitch which connect in series with coil is a normally closed contact, this contact disconnect when circuit breaker switch off. In the dashed box is circuit breaker inner accessory wire connecting drawing. |
Note: when rated control power supply voltage is DC24V, have 2 solutions:
Solution 1:Adopt DC24V shunt trip mechanism, but should according to below criteria: copper wire max length(both wire length) should according to below table, trip mechanism wire connecting terminal power supply power minimum need 50W
Wire section area | 1.5mm2 | 2.5mm2 | |
Rated control power supply voltage(Us)(DC24V) | 100 Us | 150m | 250m |
85% Us | 100m | 160m |
Solution 2:Adopt 24V middle relay control AC230V or 400V shunt trip mechanism, middle relay contact volume should not less than 1A.
Undervoltage trip mechanism (MN)
| Rated control power supply voltage (Us)(V) | AC230V,AC400V; |
Operation voltage(V) | If voltage is 35%-70% of the rated working voltage, it will make circuit breaker trip reliably; If voltage is 80% of the rated working voltage, should ensure circuit breaker switch on; if voltage lower than 35% of the rated working voltage should prevent switch on. | |
Wire connecting drawing | Note: X- wire connecting terminal row, in the dashed box is circuit breaker inner accessory wire connecting drawing. |
Warn: Undervoltage trip mechanism need power on firstly, then circuit breaker can be switch ON/OFF, otherwise circuit breaker will be destroyed.
Auxiliary contact (OF) | Conventional thermal current (Ith)(A) | 3A |
Rated working current (Ie)(A) | AC400: when Inm ≤400A is 0.3A;when 630≤Inm≤800A is 0.4A; when 100A≤Inm≤800A is 0.15A | |
Wire connecting drawing | Circuit breaker in trip-free or "OFF" position condition | |
Circuit breaker in "ON" position condition |
Alarm contact (SD) | Conventional thermal current (Ith)(A) | 3A |
Rated working current (Ie)(A) | When AC400V is 0.3A; when DC220V is 0.15A | |
Wire connecting drawing | Circuit breaker in "ON" "OFF" position condition | |
Circuit breaker in trip-free (Alarm) position condition |
Alarm module | Input voltage(V) | AC23V,AC400V |
Wire connecting drawing | Explanation: P5-P6: power supply input P3-P4: normally open; contact, contact volume AC230V,5A; P1-P2:Normally close contact, contact volume AC230v,5A; Note: in the dashed box is circuit breaker inner accessory wire connecting drawing. | |
Note: Leakage current alarm module have 2 working way, user can order according your own request: I:When electricity leaking, current leakage module send alarm signal, and circuit breaker trip simultaneously. II: When electricity leaking, current leakage module send alarm signal, but circuit breaker not trip. (II is for special place, user need deliberation when you adopt this function) |
◎Outer accessory:
Electric operation mechanism
| Input voltage(V) | AC230V,AC400V; DC110V,DC230V,DC24V | |||||
Wire connecting drawing |
Explanation: P1-P2: Connect with power supply input; SB1,SB2: operation button(provide by userself ) Note: in the dashed box is circuit breaker inner accessory wire connecting drawing. Note: Electric operation mechanism should re-close after circuit breaker tripping. | ||||||
Matched model No. | Electric operation mechanism parameter | Overall size(mm) | Installation size(mm) | ||||
Operation current (A) | Motor power (VA) | Mechanical life (times) | H | a | b | ||
KXM2LE-100 | ≤0.5A | 14 | 20000 | 89.5 | 30 | 129 | |
KXM2LE-225 | ≤0.5A | 14 | 20000 | 93 | 35 | 126 | |
KXM2LE-400 | ≤2A | 35 | 10000 | 142 | 44 | 215 | |
KXM2LE-630 | ≤2A | 35 | 10000 | 146 | 70 | 243 | |
KXM2LE-800 | ≤2A | 35 | 10000 | 146 | 70 | 243 |
Handle operation mechanism | ||||||
Model No. | KXM2LE-100 | KXM2LE-225 | KXM2LE-400 | KXM2LE-630 | KXM2LE-800 | |
Installation size (H) (mm) | 49 | 55 | 74 | 66 | 66 |
Note: Back panel wire connecting, plug in type overall and installation, hole boring size, according to accessory supplier's size, this series accessory size only for reference.