Model No.: KXR28-25/36/93
Production Capacity: 100000PCS/PER MONTH
Delivery Date: 30 days or customized
Poles Number: 3
Rated working current Ie(AC-3 (380V)): 9-95
Rated working voltage(Ue)V: 690,380
Auxiliary contact conventional free air heating current Ith (A): 10
Installation altitude: can't exceed 2000m
Installation degree: III
Means of Transport: Ocean,Land,Air
Packing: Neutral or customized
Type: Others
Brand Name: CHKX
Rated working current Ie(AC-3 (6600V)): 6.6-49
Rated isolating voltage(Ui)V: 690
Action mechanic: directing acting type
Pullution degree: III
Power supply frequency: 50,60

KXR28 series thermal overload relay (hereinafter referred tor as thermal relay) apply to AC 50Hz/60Hz, rated voltage till 660V, current 0.1-93A

KXR28 thermal overload relay series

◎Summarization

◆KXR28 series thermal overload relay (hereinafter referred tor as thermal relay) apply to AC 50Hz/60Hz, rated voltage till 660V, current 0.1-93A AC electric motor permanent working or discontinuous permanent working for overload or open-phase protection.

◆Thermal relay have open-phase protection, temperature compensation, operation indication, auto and manual reset and stop function, reliable action. Can plug-in install with contactor, also can install it independently and combined with relative AC contactor to consist of electromagnet starter.

◆According to GB14048.4, GB14048.5, IEC60947-4-1 etc standard,

KXR28 thermal overload relay series

◎Model and meaning:

 KXR28 thermal overload relay series

◎Structure feature:

KXR28 thermal overload relay series

◆Three phase sheet metal type, trip type 10A

◆Have open-phase and overload protection

◆Have setting current continuous adjustable device

◆Temperature compensation

◆Operating indication

◆Test mechanism

◆With stop button

◆With auto and manual reset button

◆On the device have separable one normally open and one normally close contact

◆Installation method: plug-in install with contactor or install independently

◎Normal working criteria

◆Altitude: not exceed 2000m

◆Surrounding air temperature: -5℃~40℃, and 24h's average temperature should lower than +35℃

◆atmospheric conditions: Atmospheric relative humidity should lower than 50% when the temperature is +40℃, higher relative humidity is acceptable when the temperature lower than +40℃, max relative humidity can reach 90% when the temperature at +20℃, should have special policy in condensation condition which may caused by temperature changing.

◆Pollution degree: III

◆Installation surface vertical gradient can't exceed 5°

◆The place should without explosion dangerous media/neurogen, and the media should without corrosive goods to metal and damage goods to isolator and no conducting dust

◆The place should have anti snow and rain device and shouldn't full of vapour

◆ The place shouldn't have obvious shake, shock and impact

◎Main technical parameter

◆Protection characteristic

Item

No.

Rated current multiple

Action time

Testing criteria

1

1.05

Non action in 2h

Cold start

Overload protection

2

1.2

Action in 2h

Hot(after No. 1) start

3

1.5

Action in 2m

Hot(after No. 1) start

4

7.2

2s﹤Tp≤40s

Cold start

Open-phase protection

5

Any two phase

Third phase

Non action in 2h

Cold start

1.0

0.9

6

1.15

2

Action in 2h

Hot(after No. 1) start

◆Trip characteristic:

This current-time curve indicate from cold to trip time and real current and setting current multiple relationship. While running current is 1.0Xle, trip time shortened to 25%. Trip curve 3 suit for 3P load, trip curve 2 suit to 2P load, for single phase load, trip curve is between 2 and 3. For general running condition, thermal trip mechanism 3PCS bimetal need to be heated. While thermal relay used for protect single phase or DC load should in series three main contact, this moment is suitable for curve 3. Three phase to load trip current is 105%-120% to setting current.

KXR28 thermal overload relay series

◎Curve drawing

 KXR28 thermal overload relay series

◆model selection and order data:

Model No.

Rated current (A) In

IEC60947-4(A)

Matched contactor model

aM

gG

KXR28-25

0.1-0.16

.25

2

KXX2-09

KXX2-12

KXX2-18

KXX2-25

KXX2-32

0.16-0.25

0.5

2

0.25-0.4

1

2

0.4-0.63

1

2

0.63-1

2

4

1-1.6

2

4

1.25-2

4

6

1.6-2.5

4

6

2.5-4

6

10

4-6

8

16

5.5-8

12

20

7-10

12

20

9-13

16

25

12-18

20

35

17-25

25

50

KXR28-36

23-32

40

63

KXX2-32

28-36

40

80

KXR28-93

23-32

40

63

KXX2-40

KXX2-50

KXX2-65

KXX2-80

KXX2-95

30-40

40

100

37-50

63

100

48-65

63

100

55-70

80

125

63-80

80

125

80-930.25

100

160

◆Main technical data:

Item

KXR28-25

KXR28-36

KXR28-93

Current degree

25

36

93

Rated isolating voltage(V)

660

660

660

Open-phase protection

with

with

with

Auto and manual reset

with

with

with

Temperature compensation

with

with

with

Trip indication

with

with

with

Testing button

with

with

with

Stop button

with

with

with

Installation method

Plug in type, independently type

Plug in type, independently type

Plug in type, independently type

Auxiliary contact

1 NO+ 2 NC

1 NO+ 2 NC

1 NO+ 2 NC

◎Overall installation size

 KXR28 thermal overload relay series

KXR28 thermal overload relay series

KXR28 thermal overload relay series

KXR28 thermal overload relay series

KXR28 thermal overload relay series

KXR28 thermal overload relay series

 

◆Accessory instruction

Name

Usage

KXR28-25 installation base

KXR28-25 as independent installation product

KXR28-36 installation base

KXR28-36 as independent installation product

KXR28-93 installation base

KXR28-93 as independent installation product

 

bigPhoto
skype Ms. RUBY XIA

Tel: 86-531-88626363
Fax: 86-531-88626268
Mobile: 135 1577 0044
Contact to this supplier

Related Search

Find more related products in following catalogs on Hisupplier.com

Company Info

JINAN STAR ELECTRIC EQUIPMENT CO., LTD [China (Mainland)]


Business Type:Manufacturer, Trading Company, Agent
City: Wenzhou
Province/State: Zhejiang
Country/Region: China (Mainland)

RUBY XIA:   skype
RUBY:   qq

You May Like: